General information |
Product type designation |
CPU 1214C DC/DC/DC |
Firmware version |
V1.0 |
● FW update possible |
Yes |
Product function |
● I&M data |
Yes; I&M0 to I&M3 |
● SysLog |
Yes |
Engineering with |
● Programming package |
STEP 7 V20 or higher |
Supply voltage |
Rated value (DC) |
|
● 24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Reverse polarity protection |
Yes |
Input current |
Current consumption (rated value) |
145 mA; CPU only |
Current consumption, max. |
1 000 mA; CPU with all expansion modules |
Inrush current, max. |
12 A; at 28.8 V DC |
I²t |
0.5 A²·s |
Output current |
for backplane bus (5 V DC), max. |
1 600 mA; Max. 5 V DC for SM and CM |
Encoder supply |
24 V encoder supply |
● 24 V |
Yes; L+ minus 4 V DC min. |
● Short-circuit protection |
Yes |
● Output current, max. |
400 mA |
Power loss |
Power loss, typ. |
3.5 W |
Memory |
Work memory |
● integrated |
1 000 kbyte |
● integrated (for program) |
250 kbyte |
● integrated (for data) |
750 kbyte |
Load memory |
● integrated |
8 Mbyte |
● Plug-in (SIMATIC Memory Card), max. |
32 Gbyte; with SIMATIC memory card |
Backup |
● present |
Yes |
● maintenance-free |
Yes |
● without battery |
Yes |
CPU processing times |
for bit operations, typ. |
37 ns; / instruction |
for word operations, typ. |
30 ns; / instruction |
for floating point arithmetic, typ. |
74 ns; / instruction |
CPU-blocks |
Number of elements (total) |
4 000; Blocks (OB, FB, FC, DB) and UDTs |
OB |
● Number of free cycle OBs |
100 |
● Number of time alarm OBs |
20 |
● Number of delay alarm OBs |
20 |
● Number of cyclic interrupt OBs |
20; with minimum OB 3x cycle of 1 ms |
● Number of process alarm OBs |
50 |
● Number of DPV1 alarm OBs |
3 |
● Number of isochronous mode OBs |
1 |
● Number of startup OBs |
100 |
● Number of asynchronous error OBs |
4 |
● Number of synchronous error OBs |
2 |
● Number of diagnostic alarm OBs |
1 |
Data areas and their retentivity |
Retentive data area (incl. timers, counters, flags), max. |
20 kbyte |
Flag |
● Size, max. |
8 kbyte; Size of bit memory address area |
Local data |
● per priority class, max. |
64 kbyte; max. 16 KB per block |
Address area |
Process image |
● Inputs, adjustable |
1 kbyte |
● Outputs, adjustable |
1 kbyte |
Hardware configuration |
Number of modules per system, max. |
10 |
Time of day |
Clock |
● Hardware clock (real-time) |
Yes |
● Backup time |
480 h; Typical |
● Deviation per day, max. |
±60 s/month at 25 °C |
Digital inputs |
Number of digital inputs |
14; Integrated |
● of which inputs usable for technological functions |
8; HSC (High Speed Counting) |
Source/sink input |
Yes |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 40 °C, max. |
14 |
Input voltage |
● Rated value (DC) |
24 V |
● for signal "0" |
5 V DC or 0.5 mA |
● for signal "1" |
15 V DC at 2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable |
0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms |
— at "0" to "1", min. |
0.1 µs |
— at "0" to "1", max. |
20 ms |
for interrupt inputs |
— parameterizable |
Yes |
for technological functions |
— parameterizable |
single phase: 6 HSCs @ 100 kHz & 2 standard @ 30 kHz, quadrature phase: 6 HSCs @ 80 kHz & 2 standard @ 20 kHz |
Cable length |
● shielded, max. |
500 m; 50 m for technological functions |
● unshielded, max. |
300 m; for technological functions: No |
Digital outputs |
Number of digital outputs |
10; 20 kHz or 100 kHz |
● of which high-speed outputs |
4; 100 kHz (Qa.0 - Qa.3) |
Limitation of inductive shutdown voltage to |
L+ (-40 V) |
Switching capacity of the outputs |
● with resistive load, max. |
0.5 A |
● on lamp load, max. |
5 W |
Output voltage |
● for signal "0", max. |
0.1 V; with 10 kOhm load |
● for signal "1", min. |
20 V |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "0" residual current, max. |
10 µA |
Output delay with resistive load |
● "0" to "1", max. |
1 µs; of the pulse outputs (Qa.0 to Qa.3), max. 1.0 µs; of the standard outputs (Qa.4 to Qb.1), max. 50 µs; |
● "1" to "0", max. |
3 µs; of the pulse outputs (Qa.0 to Qa.3), max. 3.0 µs; of the standard outputs (Qa.4 to Qb.1), max. 200 µs; |
Switching frequency |
● of the pulse outputs, with resistive load, max. |
100 kHz; 100 kHz max. (Qa.0 - Qa.3), 20 kHz max. (Qa.4 to Qb.1) |
Relay outputs |
● Number of relay outputs |
0 |
Cable length |
● shielded, max. |
500 m |
● unshielded, max. |
150 m |
Analog inputs |
Number of analog inputs |
0 |
Analog outputs |
Number of analog outputs |
0 |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
1. Interface |
Interface type |
PROFINET |
Isolated |
Yes |
automatic detection of transmission rate |
Yes |
Autonegotiation |
Yes |
Autocrossing |
Yes |
Interface types |
● RJ 45 (Ethernet) |
Yes |
● Number of ports |
2 |
● integrated switch |
Yes |
Protocols |
● IP protocol |
Yes; IPv4 |
● PROFINET IO Controller |
Yes |
● PROFINET IO Device |
Yes |
● SIMATIC communication |
Yes |
● Open IE communication |
Yes; Optionally also encrypted |
● Web server |
Yes |
● Media redundancy |
Yes |
PROFINET IO Controller |
● Transmission rate, max. |
100 Mbit/s |
Services |
— PG/OP communication |
Yes; encryption with TLS V1.3 pre-selected |
— Isochronous mode |
Yes |
— IRT |
Yes |
— PROFIenergy |
Yes; per user program |
— Prioritized startup |
Yes |
— Number of IO devices with prioritized startup, max. |
16 |
— Number of connectable IO Devices, max. |
31 |
— Of which IO devices with IRT, max. |
31 |
— Number of connectable IO Devices for RT, max. |
31 |
— of which in line, max. |
31 |
— Activation/deactivation of IO Devices |
Yes |
— Number of IO Devices that can be simultaneously activated/deactivated, max. |
8 |
— Updating time |
The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
Update time for IRT |
— for send cycle of 1 ms |
1 ms to 16 ms |
— for send cycle of 2 ms |
2 ms to 32 ms |
— for send cycle of 4 ms |
4 ms to 64 ms |
Update time for RT |
— for send cycle of 1 ms |
1 ms to 512 ms |
— for send cycle of 2 ms |
2 ms to 512 ms |
— for send cycle of 4 ms |
4 ms to 512 ms |
PROFINET IO Device |
Services |
— PG/OP communication |
Yes; encryption with TLS V1.3 pre-selected |
— Isochronous mode |
No |
— IRT |
Yes |
— PROFIenergy |
Yes; per user program |
— Shared device |
Yes |
— Number of IO Controllers with shared device, max. |
2 |
Protocols |
Supports protocol for PROFINET IO |
Yes |
PROFIsafe |
No |
PROFIBUS |
No |
OPC UA |
No |
AS-Interface |
No |
Protocols (Ethernet) |
● TCP/IP |
Yes |
● DHCP |
Yes |
● SNMP |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
Number of connections |
● Number of connections, max. |
128; via integrated interfaces of the CPU and connected CPs / CMs |
● Number of connections reserved for ES/HMI/web |
10 |
● Number of connections via integrated interfaces |
88 |
Redundancy mode |
Media redundancy |
— MRP |
Yes; as MRP redundancy manager and/or MRP client |
— MRPD |
Yes |
SIMATIC communication |
● S7 routing |
No |
● S7 communication, as server |
Yes |
● S7 communication, as client |
Yes |
Open IE communication |
● TCP/IP |
Yes |
— Data length, max. |
8 kbyte |
— several passive connections per port, supported |
Yes |
● ISO-on-TCP (RFC1006) |
Yes |
— Data length, max. |
8 kbyte |
● UDP |
Yes |
— Data length, max. |
2 kbyte; 1 472 bytes for UDP broadcast |
● DHCP |
Yes |
● DNS |
Yes |
● SNMP |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
● Encryption |
Yes; Optional |
Web server |
● supported |
Yes |
● HTTPS |
Yes |
● web API |
Yes |
— Number of sessions, max. |
30 |
● User-defined websites |
Yes |
Further protocols |
● MODBUS |
Yes |
communication functions / header |
S7 communication |
● supported |
Yes |
● as server |
Yes |
● as client |
Yes |
● User data per job, max. |
See online help (S7 communication, user data size) |
Number of connections |
● overall |
PG Connections: 4 reserved; HMI Connections: 4 reserved / 82 max; S7 Connections: 78 max; Open User Connections: 78 max; Web Connections: 2 reserved / 80 max; Total Connections: 10 reserved / 88 max |
S7 message functions |
Number of login stations for message functions, max. |
32 |
Program alarms |
Yes |
Number of configurable program messages, max. |
5 000 |
Number of loadable program messages in RUN, max. |
2 500 |
Number of simultaneously active program alarms |
|
● Number of program alarms |
600 |
● Number of alarms for system diagnostics |
100 |
● Number of alarms for motion technology objects |
160 |
Test commissioning functions |
Status/control |
● Status/control variable |
Yes |
● Variables |
Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Forcing |
● Forcing |
Yes |
Diagnostic buffer |
● present |
Yes |
Traces |
● Number of configurable Traces |
4 |
● Memory size per trace, max. |
512 kbyte |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
● RUN/STOP LED |
Yes |
● ERROR LED |
Yes |
● MAINT LED |
Yes |
Supported technology objects |
Motion Control |
Yes |
● Number of available Motion Control resources for technology objects |
800 |
● Required Motion Control resources |
|
— per speed-controlled axis |
40 |
— per positioning axis |
80 |
— per synchronous axis |
160 |
— per external encoder |
80 |
— per output cam |
20 |
— per cam track |
160 |
— per probe |
40 |
● Number of available Extended Motion Control resources for technology objects |
40 |
● Required Extended Motion Control resources |
|
— per cam (1 000 points and 50 segments) |
2; 1000 points and 1 segment |
— for each set of kinematics |
30 |
● kinematics functions |
|
— kinematics with up to 4 interpolating axes |
Yes |
— kinematics with 5 or more interpolating axes |
No |
— user-defined kinematics |
No |
— SIMATIC Safe Kinematics |
No |
● Positioning axis |
|
— Number of positioning axes at motion control cycle of 4 ms (typical value) |
10 |
— Number of positioning axes at motion control cycle of 8 ms (typical value) |
10 |
Integrated Functions |
Counter |
Yes |
● Number of counters |
8 |
● Counting frequency, max. |
100 kHz; Ia.0 to Ia.5: 100 kHz (80 kHz in quadrature mode), Ia.6 to Ib.5: 30 kHz (20 kHz in quadrature mode) |
Frequency measurement |
Yes |
PID controller |
Yes |
Number of pulse outputs |
8; individually assigned to CPU and Signal Board |
Limit frequency (pulse) |
100 kHz |
Potential separation |
Potential separation digital inputs |
● Potential separation digital inputs |
Yes; field side to logic: 707 V DC (type test) |
● between the channels |
No |
● Number of potential groups |
1 |
Potential separation digital outputs |
● Potential separation digital outputs |
Yes |
● between the channels |
No |
● Number of potential groups |
1 |
EMC |
Interference immunity against discharge of static electricity |
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 |
Yes |
— Test voltage at air discharge |
8 kV |
— Test voltage at contact discharge |
6 kV |
Interference immunity to cable-borne interference |
● Interference immunity on supply lines acc. to IEC 61000-4-4 |
Yes |
● Interference immunity on signal cables acc. to IEC 61000-4-4 |
Yes |
Interference immunity against voltage surge |
● Interference immunity on supply lines acc. to IEC 61000-4-5 |
Yes |
Interference immunity against conducted variable disturbance induced by high-frequency fields |
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 |
Yes |
Emission of radio interference acc. to EN 55 011 |
● Limit class A, for use in industrial areas |
Yes; Group 1 |
● Limit class B, for use in residential areas |
Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection |
IP degree of protection |
IP20 |
Standards, approvals, certificates |
Siemens Eco Profile (SEP) |
Siemens EcoTech |
CE mark |
Yes |
UL approval |
Yes |
cULus |
Yes |
FM approval |
No |
RCM (formerly C-TICK) |
Yes |
KC approval |
Yes |
Marine approval |
No |
Ecological footprint |
● environmental product declaration |
Yes; type 2 acc. to ISO 14021 |
Global warming potential |
— global warming potential, (total) [CO2 eq] |
68 kg |
— global warming potential, (during production) [CO2 eq] |
14.4 kg |
— global warming potential, (during operation) [CO2 eq] |
54.2 kg |
— global warming potential, (after end of life cycle) [CO2 eq] |
-0.723 kg |
product functions / security / header |
signed firmware update |
Yes |
Secure Boot |
Yes |
safely removing data |
No |
Ambient conditions |
Free fall |
● Fall height, max. |
0.3 m; five times, in product package |
Ambient temperature during operation |
● min. |
-20 °C; No condensation |
● max. |
40 °C; at max. voltages and max. specifications |
● horizontal installation, min. |
-20 °C; No condensation |
● horizontal installation, max. |
60 °C; at rated voltages, 50 % of max. specification and alternate IO active |
● vertical installation, min. |
-20 °C; No condensation |
● vertical installation, max. |
50 °C; at rated voltages, 50 % of max. specification and alternate IO active |
Ambient temperature during storage/transportation |
● min. |
-40 °C |
● max. |
70 °C |
Air pressure acc. to IEC 60068-2-13 |
● Operation, min. |
540 hPa |
● Operation, max. |
1 140 hPa |
● Storage/transport, min. |
540 hPa |
● Storage/transport, max. |
1 140 hPa |
Altitude during operation relating to sea level |
● Installation altitude, min. |
-1 000 m |
● Installation altitude, max. |
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Relative humidity |
● Operation, max. |
95 %; no condensation |
Vibrations |
● Vibration resistance during operation acc. to IEC 60068-2-6 |
3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz |
● Operation, tested according to IEC 60068-2-6 |
Yes |
Shock testing |
● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Pollutant concentrations |
● SO2 at RH < 60% without condensation |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free |
configuration / header |
configuration / programming / header |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— SCL |
Yes |
Know-how protection |
● User program protection/password protection |
Yes |
Access protection |
● protection of confidential configuration data |
Yes |
● Protection level: Write protection |
Yes |
● Protection level: Read/write protection |
Yes |
● Protection level: Complete protection |
Yes |
● User administration |
Yes; device-wide |
● Number of users |
100 |
● Number of groups |
100 |
● Number of roles |
50 |
programming / cycle time monitoring / header |
● adjustable |
Yes |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
100 mm |
Weights |
Weight, approx. |
352 g |