General information |
Product type designation |
SM 1223, DI 8x 24 V DC, DQ 8x 24 V DC 0.5A |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
from backplane bus 5 V DC, max. |
110 mA |
Digital inputs |
● from load voltage L+ (without load), max. |
4.1 mA; per channel |
Digital outputs |
● from load voltage L+, max. |
45 mA |
Power loss |
Power loss, typ. |
4 W |
Digital inputs |
Number of digital inputs |
8 |
● in groups of |
4 |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 40 °C, max. |
8 |
horizontal installation |
— up to 40 °C, max. |
8 |
— up to 50 °C, max. |
8 |
vertical installation |
— up to 40 °C, max. |
8 |
Input voltage |
● Type of input voltage |
DC |
● Rated value (DC) |
24 V |
● for signal "0" |
5 V DC or 0.5 mA |
● for signal "1" |
15 V DC at 2.5 mA |
Input current |
● for signal "0", max. (permissible quiescent current) |
1 mA |
● for signal "1", min. |
2.5 mA |
● for signal "1", typ. |
4.1 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable |
Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
for interrupt inputs |
— parameterizable |
No |
Cable length |
● shielded, max. |
500 m |
● unshielded, max. |
300 m |
Digital outputs |
Number of digital outputs |
8 |
● in groups of |
8 |
Short-circuit protection |
No; to be provided externally |
Limitation of inductive shutdown voltage to |
typ. (L+) -40 V, 1 W dissipation |
Switching capacity of the outputs |
● with resistive load, max. |
0.5 A |
● on lamp load, max. |
5 W |
Output voltage |
● Rated value (DC) |
24 V |
● for signal "0", max. |
0.1 V; with 10 kOhm load |
● for signal "1", min. |
20 V DC |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range, max. |
0.5 A |
● for signal "0" residual current, max. |
10 µA |
Output delay with resistive load |
● "0" to "1", max. |
50 µs |
● "1" to "0", max. |
200 µs |
Total current of the outputs (per group) |
horizontal installation |
— up to 50 °C, max. |
2 A; Current per mass |
Cable length |
● shielded, max. |
500 m |
● unshielded, max. |
150 m |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnoses |
● Monitoring the supply voltage |
Yes |
Diagnostics indication LED |
● DIAG LED |
Yes |
● for status of the inputs |
Yes |
● for status of the outputs |
Yes |
Potential separation |
Potential separation digital inputs |
● between the channels, in groups of |
4 |
● between the channels and backplane bus |
Yes; 707 V DC (type test) |
Potential separation digital outputs |
● between the channels, in groups of |
8 |
● between the channels and backplane bus |
Yes; 707 V DC (type test) |
Isolation |
Isolation tested with |
707 V DC (type test) |
Degree and class of protection |
IP degree of protection |
IP20 |
Standards, approvals, certificates |
Siemens Eco Profile (SEP) |
Siemens EcoTech |
CE mark |
Yes |
CSA approval |
No |
UL approval |
Yes |
cULus |
Yes |
FM approval |
No |
RCM (formerly C-TICK) |
Yes |
KC approval |
Yes |
Marine approval |
No |
Ecological footprint |
● environmental product declaration |
Yes; type 2 acc. to ISO 14021 |
Global warming potential |
— global warming potential, (total) [CO2 eq] |
40.3 kg |
— global warming potential, (during production) [CO2 eq] |
7.79 kg |
— global warming potential, (during operation) [CO2 eq] |
32.5 kg |
— global warming potential, (after end of life cycle) [CO2 eq] |
-0.089 kg |
Ambient conditions |
Free fall |
● Fall height, max. |
0.3 m; five times, in product package |
Ambient temperature during operation |
● horizontal installation, min. |
-20 °C |
● horizontal installation, max. |
60 °C; at max. voltages and max. specification |
● vertical installation, min. |
-20 °C |
● vertical installation, max. |
50 °C; at max. voltages and max. specification |
● permissible temperature change |
5°C to 55°C, 3°C / minute |
Ambient temperature during storage/transportation |
● min. |
-40 °C |
● max. |
70 °C |
Air pressure acc. to IEC 60068-2-13 |
● Operation, min. |
540 hPa |
● Operation, max. |
1 140 hPa |
● Storage/transport, min. |
540 hPa |
● Storage/transport, max. |
1 140 hPa |
Altitude during operation relating to sea level |
● Installation altitude, min. |
-1 000 m |
● Installation altitude, max. |
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Relative humidity |
● Operation at 25 ℃ without condensation, max. |
95 % |
Vibrations |
● Vibration resistance during operation acc. to IEC 60068-2-6 |
3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz |
● Operation, tested according to IEC 60068-2-6 |
Yes |
Shock testing |
● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Pollutant concentrations |
● SO2 at RH < 60% without condensation |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free |
connection method |
required front connector |
No |
Mechanics/material |
Enclosure material (front) |
|
● Plastic |
Yes |
Dimensions |
Width |
30 mm |
Height |
125 mm |
Depth |
100 mm |
Weights |
Weight, approx. |
170 g |
Approvals / Certificates |