General information |
Product type designation |
SM 1233, AI 4x 14 bit/AQ 4x 14 bit |
Supply voltage |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
Current consumption, typ. |
40 mA |
from backplane bus 5 V DC, typ. |
80 mA |
Power loss |
Power loss, typ. |
4.7 W |
Analog inputs |
Number of analog inputs |
4; Current or voltage differential inputs |
permissible input voltage for voltage input (destruction limit), max. |
35 V |
permissible input current for current input (destruction limit), max. |
40 mA |
Cycle time (all channels) max. |
0.625 ms; at 400 Hz rejection |
Input ranges |
● Voltage |
Yes; ±10V, ±5V, ±2.5V |
● Current |
Yes; 4 to 20 mA, 0 to 20 mA |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● -10 V to +10 V |
Yes |
— Input resistance (-10 V to +10 V) |
≥1 MOhm |
● -2.5 V to +2.5 V |
Yes |
— Input resistance (-2.5 V to +2.5 V) |
≥1 MOhm |
● -5 V to +5 V |
Yes |
— Input resistance (-5 V to +5 V) |
≥1 MOhm |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
— Input resistance (0 to 20 mA) |
< 290 Ω, > 270 Ω |
● 4 mA to 20 mA |
Yes |
— Input resistance (4 mA to 20 mA) |
< 290 Ω, > 270 Ω |
Cable length |
● shielded, max. |
100 m; shielded, twisted pair |
Analog outputs |
Number of analog outputs |
4; Current or voltage |
Output ranges, voltage |
● -10 V to +10 V |
Yes |
Output ranges, current |
● 0 to 20 mA |
Yes |
● 4 mA to 20 mA |
Yes |
Load impedance (in rated range of output) |
● with voltage outputs, min. |
1 000 Ω |
● with current outputs, max. |
600 Ω |
Cable length |
● shielded, max. |
100 m; shielded, twisted pair |
Analog value generation for the inputs |
Measurement principle |
successive approximation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
13 bit; + sign |
● Integration time, parameterizable |
Yes |
● Interference voltage suppression for interference frequency f1 in Hz |
40 dB, DC to 60 Hz |
Smoothing of measured values |
● parameterizable |
Yes |
● Step: None |
Yes |
● Step: low |
Yes |
● Step: Medium |
Yes |
● Step: High |
Yes |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
14 bit; Voltage: 14 bit; Current : 13 bit |
Errors/accuracies |
Temperature error (relative to input range), (+/-) |
25 °C ±0.1 % / -20 °C to 60 °C ±0.2 % of the full-scale deflection |
Temperature error (relative to output range), (+/-) |
25 °C ±0.3 % / -20 °C to 60 °C ±0.6 % of the full-scale deflection |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input range, (+/-) |
0.1 % |
● Current, relative to input range, (+/-) |
0.1 % |
● Voltage, relative to output range, (+/-) |
0.3 % |
● Current, relative to output range, (+/-) |
0.3 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Common mode voltage, max. |
2 V |
Interrupts/diagnostics/status information |
Diagnostics function |
Yes |
Alarms |
● Diagnostic alarm |
Yes |
Diagnoses |
● Monitoring the supply voltage |
Yes |
● Wire-break |
Yes |
● Short-circuit |
Yes |
Diagnostics indication LED |
● DIAG LED |
Yes |
● for status of the inputs |
Yes |
● for status of the outputs |
Yes |
Potential separation |
Potential separation analog inputs |
● between the channels and the power supply of the electronics |
No |
Potential separation analog outputs |
● between the channels and the power supply of the electronics |
No |
Degree and class of protection |
IP degree of protection |
IP20 |
Standards, approvals, certificates |
Siemens Eco Profile (SEP) |
Siemens EcoTech |
CE mark |
Yes |
CSA approval |
No |
UL approval |
Yes |
cULus |
Yes |
FM approval |
No |
RCM (formerly C-TICK) |
Yes |
KC approval |
Yes |
Marine approval |
No |
Ecological footprint |
● environmental product declaration |
Yes; type 2 acc. to ISO 14021 |
Global warming potential |
— global warming potential, (total) [CO2 eq] |
32.2 kg |
— global warming potential, (during production) [CO2 eq] |
7.96 kg |
— global warming potential, (during operation) [CO2 eq] |
24.5 kg |
— global warming potential, (after end of life cycle) [CO2 eq] |
-0.358 kg |
Ambient conditions |
Free fall |
● Fall height, max. |
0.3 m; five times, in product package |
Ambient temperature during operation |
● min. |
-20 °C |
● max. |
40 °C; at max. voltages and max. specifications |
● horizontal installation, min. |
-20 °C |
● horizontal installation, max. |
60 °C; at rated voltages, 50 % of max. specification and alternate IO active |
● vertical installation, min. |
-20 °C |
● vertical installation, max. |
50 °C; at rated voltages, 50 % of max. specification and alternate IO active |
Ambient temperature during storage/transportation |
● min. |
-40 °C |
● max. |
70 °C |
Air pressure acc. to IEC 60068-2-13 |
● Operation, min. |
540 hPa |
● Operation, max. |
1 140 hPa |
● Storage/transport, min. |
540 hPa |
● Storage/transport, max. |
1 140 hPa |
Altitude during operation relating to sea level |
● Installation altitude, min. |
-1 000 m |
● Installation altitude, max. |
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Relative humidity |
● Operation at 25 ℃ without condensation, max. |
95 % |
Vibrations |
● Vibration resistance during operation acc. to IEC 60068-2-6 |
3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz |
● Operation, tested according to IEC 60068-2-6 |
Yes |
Shock testing |
● tested according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Pollutant concentrations |
● SO2 at RH < 60% without condensation |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free |
connection method |
required front connector |
No |
Mechanics/material |
Enclosure material (front) |
|
● Plastic |
Yes |
Dimensions |
Width |
30 mm |
Height |
125 mm |
Depth |
100 mm |
Weights |
Weight, approx. |
174 g |